M&M FDT 1.2.1 Online Specification
 FDTProfinetIOIdentSchema definition


Interfaces and Methods   -   Schemas   -   FDT Specification   -   Quicklinks   -   Abbreviations

FDTProfinetIOIdentSchema

Available since PNIO Annex for FDT 1.2.1

Download ProfiNet IO Annex from FDT Group Homepage.

Available since FDT 1.2
Available since FDT 1.2.1
Available since FDT 1.2 and modified or extended in FDT 1.2.1
Specification description (mouse over)
dtmINSPECTOR related hint (mouse over)
Comment by M&M (mouse over)
Link to definition
<Schema name="FDTProfinetIOIdentSchema"   xmlns="urn:schemas-microsoft-com:xml-data" xmlns:dt="urn:schemas-microsoft-com:datatypes" >
      <!-- Definition of Attributes -->
     <AttributeType name="schemaVersion" dt:type="number" default="1.00" />
     <AttributeType name="busProtocol"
dt:type="enumeration" dt:values="protocol_DCP protocol_IM" />
      <!-- -->
      <!-- Profinet IO -->
      <!-- DCP Identify Information -->
      <!-- -->
      <!-- -->
     <AttributeType name="nameOfStation"
dt:type="string" />
     <AttributeType name="ipAddress"
dt:type="string" />
     <AttributeType name="ipSubnetMask"
dt:type="string" />
     <AttributeType name="ipDefaultGateway"
dt:type="string" />
     <AttributeType name="macAddress"
dt:type="string" />
     <AttributeType name="deviceRole"
dt:type="enumeration" dt:values="ProfinetIO_Controller ProfinetIO_Device ProfinetIO_MultiDevice ProfinetIO_Supervisor" />
      <!-- -->
      <!-- Profinet IO -->
      <!-- I&M information -->
      <!-- -->
      <!-- -->
      <!-- I&M 0 Element 1 -->
     <AttributeType name="orderId"
dt:type="string" dt:maxLength="20" />
      <!-- I&M 0 Element 2 -->
     <AttributeType name="serialNumber"
dt:type="string" dt:maxLength="16" />
      <!-- I&M 0 Element 3 unique serial number -->
     <AttributeType name="hardwareRevision"
dt:type="string" />
      <!-- I&M 0 Element 4 HARDWARE_REVISION - 2 Octets transformed to string (to be consistent to PA_I&M) -->
     <AttributeType name="softwareRevision"
dt:type="string" />
      <!-- I&M 0 Element 5 SOFTWARE_REVISION - 4 Octets : 4 Octets - 1 char + 3 unsigned 8 , e.g.: V1.2.3 -->
     <AttributeType name="profileID"
dt:type="ui2" />
      <!-- I&M 0 Element 7 PROFILE_ID -->
     <AttributeType name="profileSpecificType"
dt:type="ui2" />
      <!-- I&M 0 Element 8 PROFILE_SPECIFIC_TYPE - MSB = BLOCK_OBJECT, LSB = PARENT_CLASS -->
     <AttributeType name="tagFunction"
dt:type="string" dt:maxLength="32" />
      <!-- I&M1 element 1 TAG_FUNCTION - mapped to semantic of IdTag -->
     <AttributeType name="tagLocation"
dt:type="string" dt:maxLength="22" />
      <!-- I&M1 element 2 TAG_LOCATION -->
      <!-- -->
      <!-- -->
      <!-- general -->
      <!-- -->
     <AttributeType name="idDTMSupportLevel"
dt:type="enumeration" dt:values="genericSupport profileSupport blockspecificProfileSupport specificSupport" />
     <AttributeType name="manufacturerSpecificExtension"
dt:type="string" />
     <AttributeType name="match"
dt:type="string" />
     <AttributeType name="nomatch"
dt:type="string" />
     <ElementType name="RegExpr"
content="empty" model="closed" >
          <attribute type="match"
  required="no" />
          <attribute type="nomatch"   required="no" />
     </ElementType>
</Schema>

© by M&M Software GmbH, parts of this website taken from FDT Interface Specification Version 1.2.1, © by FDT Group, AISBL.
This website is published for support of M&M products as granted in license conditions, chapter 2.1.
Last updated 2015-02-05 15:18