M&M FDT 1.2.1 Online Specification
 FDTProfibusChannelParameterSchema definition


Interfaces and Methods   -   Schemas   -   FDT Specification   -   Quicklinks   -   Abbreviations

FDTProfibusChannelParameterSchema

Available since FDT 1.2.0.0

Available since FDT 1.2
Available since FDT 1.2.1
Available since FDT 1.2 and modified or extended in FDT 1.2.1
Specification description (mouse over)
dtmINSPECTOR related hint (mouse over)
Comment by M&M (mouse over)
Link to definition
<Schema name="FDTProfibusChannelParameterSchema" xmlns="urn:schemas-microsoft-com:xml-data" xmlns:dt="urn:schemas-microsoft-com:datatypes" xmlns:fdt="x-schema:FDTDataTypesSchema.xml" xmlns:appId="x-schema:FDTApplicationIdSchema.xml" >
      <!-- Definition of Attributes -->
     <AttributeType name="schemaVersion" dt:type="number" default="1.21" />
     <AttributeType name="api"
dt:type="ui1" />
     <AttributeType name="bitLength"
dt:type="ui4" />
     <AttributeType name="bitPosition"
dt:type="ui4" />
     <AttributeType name="frameApplicationTag"
dt:type="string" />
     <AttributeType name="gatewayBusCategory"
dt:type="uuid" />
     <AttributeType name="invalidBit"
dt:type="ui4" />
     <AttributeType name="index"
dt:type="ui1" />
     <AttributeType name="logic"
dt:type="enumeration" dt:values="positive negative" />
     <AttributeType name="number"
dt:type="ui4" />
     <AttributeType name="protectedByChannelAssignment"
dt:type="boolean" />
     <AttributeType name="simulationBit"
dt:type="ui4" />
     <AttributeType name="statusChannel"
dt:type="boolean" />
     <AttributeType name="substituteValueBit"
dt:type="ui4" />
     <AttributeType name="slotNumber"
dt:type="ui1" />
      <!-- Definition of Elements -->
     <ElementType name="DpAddress"
content="empty" model="closed" >
          <attribute type="fdt:nodeId"
  required="no" />
          <attribute type="bitPosition"   required="yes" />
          <attribute type="bitLength"   required="yes" />
     </ElementType>
     <ElementType name="DpV1Address" content="empty" model="closed" >
          <attribute type="fdt:nodeId"
  required="no" />
          <attribute type="api"   required="yes" />
          <attribute type="slotNumber"   required="yes" />
          <attribute type="index"   required="yes" />
          <attribute type="bitPosition"   required="no" />
          <attribute type="bitLength"   required="no" />
     </ElementType>
     <ElementType name="StatusInformation" content="empty" model="closed" >
          <attribute type="fdt:nodeId"
  required="no" />
          <attribute type="logic"   required="yes" />
          <attribute type="invalidBit"   required="no" />
          <attribute type="simulationBit"   required="no" />
          <attribute type="substituteValueBit"   required="no" />
     </ElementType>
     <ElementType name="FDTChannel" content="eltOnly" model="closed" order="seq" >
          <attribute type="fdt:nodeId"
  required="no" />
          <attribute type="fdt:tag"   required="yes" />
          <attribute type="fdt:id"   required="yes" />
          <attribute type="fdt:descriptor"   required="no" />
          <attribute type="protectedByChannelAssignment"   required="yes" />
          <attribute type="number"   required="yes" />
          <attribute type="fdt:dataType"   required="yes" />
          <attribute type="fdt:signalType"   required="yes" />
          <attribute type="frameApplicationTag"   required="no" />
          <attribute type="appId:applicationId"   required="no" />
          <element type="fdt:SemanticInformation"   minOccurs="0" maxOccurs="*" />
          <element type="fdt:BitEnumeratorEntries"   minOccurs="0" maxOccurs="1" />
          <element type="fdt:EnumeratorEntries"   minOccurs="0" maxOccurs="1" />
          <element type="fdt:Unit"   minOccurs="0" maxOccurs="1" />
          <element type="DpAddress"   minOccurs="0" maxOccurs="1" />
          <element type="DpV1Address"   minOccurs="0" maxOccurs="1" />
          <element type="StatusInformation"   minOccurs="0" maxOccurs="1" />
          <element type="fdt:Alarms"   minOccurs="0" maxOccurs="1" />
          <element type="fdt:Ranges"   minOccurs="0" maxOccurs="1" />
          <element type="fdt:Deadband"   minOccurs="0" maxOccurs="1" />
          <element type="fdt:SubstituteValue"   minOccurs="0" maxOccurs="1" />
          <element type="fdt:StructuredElements"   minOccurs="0" maxOccurs="1" />
           <!-- should be used if the data type is structured -->
     </ElementType>
     <ElementType name="FDTChannelType" content="eltOnly" model="closed" >
          <attribute type="fdt:nodeId"
  required="no" />
          <element type="fdt:VersionInformation"   minOccurs="1" maxOccurs="1" />
          <attribute type="gatewayBusCategory"   required="no" />
          <attribute type="statusChannel"   required="no" />
     </ElementType>
     <ElementType name="FDT" content="eltOnly" model="closed" >
          <attribute type="schemaVersion"
  required="no" />
          <attribute type="fdt:nodeId"   required="no" />
          <element type="FDTChannelType"   minOccurs="1" maxOccurs="1" />
          <element type="FDTChannel"   minOccurs="1" maxOccurs="1" />
     </ElementType>
</Schema>

© by M&M Software GmbH, parts of this website taken from FDT Interface Specification Version 1.2.1, © by FDT Group, AISBL.
This website is published for support of M&M products as granted in license conditions, chapter 2.1.
Last updated 2015-02-05 15:18
Email: FDT Technical Support Line.