Interfaces and Methods - Schemas - FDT Specification - Quicklinks - Abbreviations | |||
| Up to 4 FDT Interface Specification 4.10.7.1 Redundancy Scenarios 4.10.7.2 Redundancy Support in Frame Application 4.10.7.3 Parent Component for Redundant Fieldbus 4.10.7.4 Redundancy Support in Device-DTM 4.10.7.5 Scan and Redundant Slaves 4.10.7.6 Topology Import-/Export | 4.10.7.2 Redundancy Support in Frame ApplicationThe DTMs able to handle slave redundancy can be used by any FDT Frame Application without need for specific redundancy support or knowledge. A FDT Frame Application may optionally implement the IDtmRedundancyEvents interface. Such a Frame Application is then able to display redundant slaves in it's topology view, e.g. a field device connected to two different lines or by using specific device icons within a topology treeview. Within a Frame Application not implementing the IDtmRedundancyEvents interface a DTM representing a redundant slave can not be distinguished within the topology view. But the DTM and the parent component themselves typically display additional information, e.g. additional fieldbus addresses. Nevertheless within such a Frame Application these DTMs provide full functionality with regard to fieldbus redundancy. As a redundant slave is represented by one DTM instance no additional functionality with regard to dataset synchronization or multiuser is required. | ||
© by M&M Software GmbH, parts of this website taken from FDT Interface Specification Version 1.2.1, © by FDT Group, AISBL. This website is published for support of M&M products as granted in license conditions, chapter 2.1. Last updated 2015-02-05 15:17 Email: FDT Technical Support Line. | |||