M&M FDT 1.2.1 Online Specification
 IFdtCommunication::Abort() method information


Interfaces and Methods   -   Schemas   -   FDT Specification   -   Quicklinks   -   Abbreviations

4.5.3.1 IFdtCommunication::Abort()


This method can be called in the states:          

HRESULT Abort (
[in] FdtXmlDocument fieldbusFrame
);


Description:
Aborts a communication link to a device without any response.

Parameters:
fieldbusFrameFieldbus-protocol-specific information how to abort. The structure is specified by a fieldbus specific schema e.g. like FDTHARTCommunicationSchema or FDTProfibusCommunicationSchema


Return Value:


Behavior:
The method sends the abort to the next communication component or to the connected device, terminates all pending requests and returns without waiting for a result. The termination of the connection will not be confirmed.

Comments:
-/-


Related dtmINSPECTOR hints:
Thomas Weller
created on 2006-10-25, last updated on 2006-10-25
The dtmINSPECTOR related test is MainDataExchangeAbort. It is tested whether the DTM does not send a OnTransactionResponse() for a TransactionRequest() after Abort() has been called.


© by M&M Software GmbH, parts of this website taken from FDT Interface Specification Version 1.2.1, © by FDT Group, AISBL.
This website is published for support of M&M products as granted in license conditions, chapter 2.1.
Last updated 2015-02-05 15:17
Email: FDT Technical Support Line.